Three-Phase • 400V • Copper Cable • Current Input

Calculate Wire Cross-Section with Current in Amps

Calculate the required wire cross-section for a copper cable on a three-phase system based on current, cable length, cos φ and permissible voltage drop.

Calculation Values

Note: This calculation is a technically sound simplification typical of online calculators. For practical sizing, standards, installation method, temperature, grouping, protective devices, cable type and manufacturer specifications must also be checked.
Advertisement

Formula Used

For three-phase systems:

A = (√3 × L × I × cos φ) / (κ × ΔU)

Here, A is the conductor cross-section in mm², L the one-way cable length in meters, I the current in amps, κ the conductivity of copper, defaulting to 58, and ΔU the permissible voltage drop in volts. The power factor cos φ is properly accounted for in the current and voltage drop calculation.

Advertisement

Practical guidance

Compare a three-phase copper cable using known current

The entered line current goes directly into the voltage-drop formula; no current is inferred from power.

Input values explained

Current
Enter the expected operating current, not a fuse rating. Motors and electronic power supplies may draw much higher starting or peak currents.
Cable length
Enter the one-way distance from supply point to load. The required return path is already represented by the selected formula.
Voltage
Enter the line-to-line voltage between two phases. This is commonly 400 V in low-voltage systems; 230 V is not the correct input here.
Power factor cos φ
cos φ is the ratio of active to apparent power. It is close to 1 for resistive heating loads; use the data-sheet value for motors and transformers.
Permitted voltage drop
This percentage limits the calculated voltage loss. It is a design assumption and must suit the circuit and applicable requirements.
Conductivity κ
κ is the calculation value for the conductor material. Common approximations are 58 for copper and 37 for aluminium; heating increases actual resistance.

Example: 32 A over 40 m

For 32 A, 400 V three-phase, 40 m copper, cos φ 0.90 and 3% voltage drop, the minimum is calculated.

A = (√3 × 40 × 32 × 0.90) ÷ (58 × 12) ≈ 2.87 mm²

The next standard value is 4 mm². Depending on installation method, 32 A may require a larger conductor for thermal reasons.

Check ampacity separately

Meeting a voltage-drop target does not prove acceptable conductor temperature or protective-device operation.

Calculation limits

  • Starting current, harmonics and phase imbalance are not modelled.
  • Loaded-core count and installation correction factors are absent.