Three-Phase • 400V • Copper Cable

Calculate Wire Cross-Section for Three-Phase 400V

Calculate the required wire cross-section for a copper cable based on power, cable length, cos φ and permissible voltage drop.

Calculation Values

Note: This calculation is a technically sound simplification typical of online calculators. For practical sizing, standards, installation method, temperature, grouping, protective devices, cable type and manufacturer specifications must also be checked.
Advertisement

Formula Used

For three-phase systems:

I = P / (√3 × U × cos φ)

A = (√3 × L × I × cos φ) / (κ × ΔU)

Here, A is the conductor cross-section in mm², L the one-way cable length in meters, I the current in amps, κ the conductivity of copper, defaulting to 58, and ΔU the permissible voltage drop in volts. The power factor cos φ is properly accounted for in the current and voltage drop calculation.

Advertisement

Practical guidance

Calculate a 400 V copper cable from power and voltage drop

The page derives balanced current and then the minimum cross-section that meets the selected voltage-drop target.

Input values explained

Power in kilowatts
Enter the electrical active power in kW. One kW equals 1,000 W; motor output power and electrical input power are not necessarily the same.
Cable length
Enter the one-way distance from supply point to load. The required return path is already represented by the selected formula.
Voltage
Enter the line-to-line voltage between two phases. This is commonly 400 V in low-voltage systems; 230 V is not the correct input here.
Power factor cos φ
cos φ is the ratio of active to apparent power. It is close to 1 for resistive heating loads; use the data-sheet value for motors and transformers.
Permitted voltage drop
This percentage limits the calculated voltage loss. It is a design assumption and must suit the circuit and applicable requirements.
Conductivity κ
κ is the calculation value for the conductor material. Common approximations are 58 for copper and 37 for aluminium; heating increases actual resistance.

Example: 11 kW over 25 m

At 400 V, 11 kW, cos φ 0.90 and 3%, 12 V of loss is allowed.

I ≈ 17.64 A; A = (√3 × 25 × 17.64 × 0.90) ÷ (58 × 12) ≈ 0.99 mm²

Voltage drop indicates 1.5 mm². Thermal ampacity will often require a larger size for a real 11 kW circuit.

State the result as a voltage-drop minimum

Only comparison with ampacity and protective requirements can produce a defensible final cable size.

Calculation limits

  • Motor starting, harmonics and neutral loading are excluded.
  • Cable type, temperature, installation method and protection are unknown.