Calculate Wire Cross-Section with Current in Amps

Calculate the required wire cross-section for a copper cable on a single-phase system based on current, cable length, cos φ and permissible voltage drop.

Calculation Values

Note: This calculation is a technically sound simplification typical of online calculators. For practical sizing, standards, installation method, temperature, grouping, protective devices, cable type and manufacturer specifications must also be checked.
Advertisement

Formula Used

For single-phase systems:

A = (2 × L × I × cos φ) / (κ × ΔU)

Here, A is the conductor cross-section in mm², L the one-way cable length in meters, I the current in amps, κ the conductivity of copper, defaulting to 58, and ΔU the permissible voltage drop in volts. The power factor cos φ is properly accounted for in the current and voltage drop calculation.

Advertisement

Practical guidance

Check a 230 V copper cable from known current

Known operating current and one-way length are used with factor 2 for the complete outgoing and return path.

Input values explained

Current
Enter the expected operating current, not a fuse rating. Motors and electronic power supplies may draw much higher starting or peak currents.
Cable length
Enter the one-way distance from supply point to load. The required return path is already represented by the selected formula.
Voltage
Enter the voltage between line and neutral. This is commonly 230 V in low-voltage systems.
Power factor cos φ
cos φ is the ratio of active to apparent power. It is close to 1 for resistive heating loads; use the data-sheet value for motors and transformers.
Permitted voltage drop
This percentage limits the calculated voltage loss. It is a design assumption and must suit the circuit and applicable requirements.
Conductivity κ
κ is the calculation value for the conductor material. Common approximations are 58 for copper and 37 for aluminium; heating increases actual resistance.

Example: 16 A over 25 m

For 16 A, 230 V, 25 m copper, cos φ 0.90 and 3%, the available voltage loss is 6.9 V.

A = (2 × 25 × 16 × 0.90) ÷ (58 × 6.9) ≈ 1.80 mm²

The calculator selects 2.5 mm². Thermal ampacity and protection still need independent verification.

Voltage drop is one design check

Long runs may be governed by voltage drop; short runs are often governed by ampacity. The stricter requirement wins.

Calculation limits

  • Contact resistance is excluded.
  • Installation method and fault-disconnection conditions can require a larger size.