Calculate Wire Cross-Section for Single-Phase 230V

Calculate the required wire cross-section for a copper cable on a single-phase system based on power, cable length, cos φ and permissible voltage drop.

Calculation Values

Note: This calculation is a technically sound simplification typical of online calculators. For practical sizing, standards, installation method, temperature, grouping, protective devices, cable type and manufacturer specifications must also be checked.
Advertisement

Formula Used

For single-phase systems:

I = P / (U × cos φ)

A = (2 × L × I × cos φ) / (κ × ΔU)

Here, A is the conductor cross-section in mm², L the one-way cable length in meters, I the current in amps, κ the conductivity of copper, defaulting to 58, and ΔU the permissible voltage drop in volts. The power factor cos φ is properly accounted for in the current and voltage drop calculation.

Advertisement

Practical guidance

Size a copper cable for a 230 V load

This page converts active power into single-phase current and then calculates the cross-section required by the selected voltage-drop limit.

Input values explained

Power in kilowatts
Enter the electrical active power in kW. One kW equals 1,000 W; motor output power and electrical input power are not necessarily the same.
Cable length
Enter the one-way distance from supply point to load. The required return path is already represented by the selected formula.
Voltage
Enter the voltage between line and neutral. This is commonly 230 V in low-voltage systems.
Power factor cos φ
cos φ is the ratio of active to apparent power. It is close to 1 for resistive heating loads; use the data-sheet value for motors and transformers.
Permitted voltage drop
This percentage limits the calculated voltage loss. It is a design assumption and must suit the circuit and applicable requirements.
Conductivity κ
κ is the calculation value for the conductor material. Common approximations are 58 for copper and 37 for aluminium; heating increases actual resistance.

Example: 3.5 kW over 25 m

A 230 V load draws 3.5 kW at cos φ 0.90 through 25 m of copper with a 3% voltage-drop target.

I ≈ 16.91 A; A = (2 × 25 × 16.91 × 0.90) ÷ (58 × 6.9) ≈ 1.90 mm²

The next standard size is 2.5 mm². The circuit must still meet installation-method, protection and disconnection requirements.

Why outgoing and return paths matter

Factor 2 represents line and return conductors. Enter the one-way route length; do not double it manually.

Calculation limits

  • Loop impedance and thermal ampacity are not verified.
  • High-inrush and nonlinear loads require additional assessment.